WaveStar® PowerHub® 2 PDU

Available in sizes ranging from 375 – 1.25 MVA,  PowerHub 2 is a powerhouse PDU. It’s industry leading 60” wide x 40” deep true front access cabinet makes it the smallest footprint in its class.  Known for its centralized brazed bus system the PowerHub 2 provides up to (12) 400A or (16) 225A 100% rated sub feed distribution breakers.  It’s compartmentalized design isolates controls and high voltage components which simplifies maintenance and increases operator safety.  Front Access Infrared Scanning ensures maximum reliability and uptime for your mission critical facility. For pro-active management of power usage and availability, the PowerHub 2 utilizes Intelligent Power Monitoring through the WaveStar® BCMS, or Branch Circuit Monitoring System including a class-leading 7” color touchscreen display.


Product Features & Benefits

Four-tier True Front Access Cabinet   
The 60" wide x 40" deep Four-tier True Front Access Cabinet maximizes square footage utilization and enables all operation, maintenance and service from the front of the PDU.


Front Access Infrared Scanning  
Full swing out front doors and an unobstructed view cabinet design enable infrared scanning of all bolted line and load connections.


375 to 1MVA DOE2016 Transformer 
PowerHub 2 offers DOE-compliant transformers in sizes from 375 to 1MVA.  Up to 1.25 MVA High Efficiency Transformer.


Future-Proof Dual and Triple Output Transformer  
PowerHub 2 offers dual and triple output transformers allowing easy migration to different voltages, future-proofing your data center.

Compartmentalized Controls & High Voltage Enclosures  
Isolated compartments for both controls and high voltage components simplifies maintenance and increase operator safety.

Intelligent Power Monitoring 
PDI’s Branch Circuit Monitoring System (BCMS) allows for the pro-active management of power usage and availability.

Brazed Transformer Connections 
Brazed transformer connections decrease electrical resistance and eliminate the need for transformer infrared scanning. 

Centralized Bus Design 
PowerHub 2 provides up-to 12 (400A) and up-to 16 (225A) sub feed distribution breakers via a centralized bus design. 

Adaptable Service Entrances 
Landing service entrance cables has never been easier with Top/Bottom Entry/Exit configurations. 